Heat Pump Repair in Dillsburg, PA: Correcting Faulty Mini-Split Flare Connections

Metro HVAC · From the field

Dillsburg, Pennsylvania

No heat.
No cooling.
Time to find out why.

A Daikin ductless heat pump had stopped providing heating and cooling. The Metro HVAC team found improperly made refrigerant flare connections—and got to work correcting them.

Daikin outdoor mini-split connected to service equipment during Metro HVAC’s heat pump repair in Dillsburg, PA.
A real Metro HVAC service callDaikin ductless heat pump · Dillsburg, PA
200 micronsVacuum reached during evacuation
6 lb 7 ozFactory refrigerant charge weighed in
All headsIndoor mini-split units cleaned

A system that wasn’t heating or cooling.

When a heat pump stops doing both jobs, identifying the cause comes first. Metro HVAC visited this Dillsburg home to diagnose the system and determine what needed repair.

Flare connections that needed correction.

Flare connections join refrigerant tubing to components of a ductless system. On this Daikin unit, they had not been made correctly and needed to be redone.

Small details. Careful service.

Our work covered the refrigerant connections, the indoor heads, and the steps needed to prepare the circuit for an accurately measured recharge.

  1. Recover

    Refrigerant recovered

    We recovered the refrigerant before opening the refrigerant circuit.

  2. Repair

    Flare connections remade

    Our technicians remade the faulty flares to address the connection issue found during diagnosis.

  3. Clean

    Every indoor head cleaned

    We cleaned all of the indoor mini-split heads as part of the service.

  4. Test

    Nitrogen pressure test

    After redoing the flares, we performed a nitrogen pressure test to check the refrigerant circuit for leaks.

  5. Evacuate

    Vacuum down to 200 microns

    We evacuated the system before adding refrigerant. Evacuation removes air and moisture from the refrigerant circuit.

  6. Charge

    Factory charge weighed in

    We recharged this system with its specified factory refrigerant charge of 6 pounds, 7 ounces.

Specific to this repair: The 200-micron reading and 6 lb 7 oz charge describe this job. Charging requirements depend on the equipment and installation; a vacuum reading alone does not replace leak testing or the other service steps.

Address the cause behind the symptoms.

This Dillsburg project involved correcting the faulty flares, cleaning the indoor heads, performing a nitrogen test, evacuating the refrigerant circuit, and measuring the charge.

If your ductless heat pump isn’t heating or cooling, a diagnosis can help determine what needs attention. Similar symptoms can have different causes, so the repair should follow the findings on your equipment.

Metro HVAC · Dillsburg heat pump service

Let’s get to the source of your comfort problem.

Need heat-pump or mini-split repair in Dillsburg, PA? Contact Metro HVAC to schedule a diagnostic visit.